VENTING INSTALLATION

SS38 Direct Vent Gas Stove

Horizontal termination configurations

Figures 15 through 17 show different configurations for venting with horizontal termination. Each figure includes a chart with vertical minimum/maximum and horizontal maximum dimensions which must be met. All horizontal terminations require a 1/4" rise per 12" of horizontal run.

NOTE: Add 1/4" rise per 12" horizontal length of pipe.

Table 1 - Horizontal Venting

Vertical (V) Minimum

Horizontal (H) Maximum

5'

30"

6'

8'

8'

20'

NOTE: This configuration is for use with corner installation also.

Figure 15 -

Horizontal Termination Configuration for Rigid

Venting Using One 90° Elbow

HOT

V

H

ST1105

H1

Table 2 - Horizontal Venting with Two (2) 90° Elbows

Vertical (V)

Horizontal (H)

Horizontal (H) +

Minimum

 

Horizontal (H1) Max.

7'

4' Max.

8'

8'

6' Max.

12'

9'

8' Min.

20'

20'

8' Max.

20'

NOTE: Add 1/4" rise per 12" horizontal length of pipe.

V

H

ST1106

Figure 16 -

Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows

46D0232

15