SS38 Direct Vent Gas Stove

VENTING INSTALLATION

Level

Cut Hole 1/8" Larger than Support Box when Projected onto Roofline.

Cathedral Ceiling

Support Box

2" Minimum Below Finished Ceiling

ST1108

ST1109

Apply Non-hardening

Mastic Under all Edges of

Support Box before Nailing

Figure 22 -

Installed Cathedral Ceiling Support Box

Figure 21 -

Cathedral Ceiling Support Box Installation

VERTICAL TERMINATION CONFIGURA- TIONS

Figures 23 through 26 show four different configurations for vertical termination.

IMPORTANT: You must install a restrictor on all vertical installations.

NOTE: Install restrictor into 4" collar of stove or first vent section as shown.

Table 5 - Vertical Venting with Two (2) 90° Elbows

Vertical (V) Minimum

Horizontal (H) Maximum

 

 

8'

2'

 

 

9'

4'

 

 

10'

6'

 

 

11'

8'

V

23'

8'

 

 

Figure 23 -

 

 

 

 

 

 

Vertical Rigid Venting Configuration Using Two

 

 

90° Elbows

 

 

 

 

 

 

 

NOTE: Install restrictor into 4" collar of stove or first vent secton as shown.

H

ST1110

18

46D0232

Page 18
Image 18
Monessen Hearth SS38 operating instructions Vertical Termination CONFIGURA- Tions