DCA-100SSVU — LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's name plate,

NOTE approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

 

Type Of Load

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 100

At 200

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

 

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA-100SSVU— OPERATION AND PARTS MANUAL — REV. #0 (11/05/07) — PAGE 27

Page 27
Image 27
Multiquip operation manual DCA-100SSVU Load Application, Single Phase Load, Three Phase Load

DCA-100SSVU specifications

The Multiquip DCA-100SSVU is a powerful and versatile portable generator that is designed to meet the needs of a wide range of applications. Ideal for construction sites, events, and emergency power needs, this generator combines reliability with excellent performance.

One of the standout features of the DCA-100SSVU is its robust 100 kVA output, making it suitable for powering larger equipment and multiple tools simultaneously. This generator is equipped with a rugged and durable construction, ensuring it can withstand the rigors of outdoor use. Its compact design allows for easy transport and placement in tight spaces, making it an ideal choice for contractors and event planners who need a reliable power source.

The DCA-100SSVU utilizes a highly efficient diesel engine, which not only provides high performance but also ensures lower fuel consumption compared to traditional gasoline generators. This fuel efficiency translates into cost savings over time, especially for users who need extended run times. Furthermore, the generator boasts a large fuel tank capacity, allowing for longer operational periods between refuels, enhancing productivity at job sites.

In terms of technology, the DCA-100SSVU incorporates advanced sound attenuation features that significantly reduce noise levels, making it suitable for use in noise-sensitive environments such as urban areas or residential neighborhoods. Its low noise operation is not only beneficial for compliance with local regulations but also for maintaining a comfortable working environment.

The generator also comes with a user-friendly control panel, equipped with indicators for monitoring fuel levels, output voltage, and engine status, ensuring that operators can easily manage the generator's performance. This intuitive design minimizes the learning curve for new users and enhances operational efficiency.

Safety features are paramount in the DCA-100SSVU design. It includes protective circuits against overloads and short circuits, ensuring that both the generator and connected equipment remain safe during operation. Moreover, the generator is designed with ample ventilation, preventing overheating and ensuring reliable performance even in demanding conditions.

In summary, the Multiquip DCA-100SSVU is a reliable and efficient portable generator that offers impressive power output, fuel efficiency, low noise levels, and a host of user-friendly features. It is an excellent choice for professionals who require a dependable power source for various applications, making it a standout option in the generator market.