DCA-100SSVU — GENERATOR START-UP PROCEDURE (MANUAL)

DCA-100SSVU — GENERATOR START-UP PROCEDURE (MANUAL)

Before Starting

CAUTION - LETHAL EXHAUST HAZARD

The engine's exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WARNING - STARTINGTHE GENERATOR

NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

1.Place the main, G.F.C.I., and aux. circuit breakers (Figure 38) in the OFF position prior to starting the engine.

Figure 38. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Make sure the the voltage change-over board has been configured for the desired output voltage.

3.Connect the load to the receptacles or the output terminal lugs as shown in Figure 13. These load connection points can be found on the output terminal panel and the output terminal panel’s hard wire hookup panel.

4.The output terminal lugs are protected by a plastic cover. Remove this cover to gain access to the terminals. Tighten terminal nuts securely to prevent load wires from slipping out.

5.Close all engine enclosure doors (Figure 39).

Manual Start-up Procedure

1.Place the engine speed switch (Figure 41) in the “LOW ” (down) position.

Figure 41. Engine Speed Switch (Low)

2.Once the engine glow plugs have been warmed, place the MPEC Control Switch in the MANUAL position to start the engine (Figure 42).

Figure 42. MPEC Control Switch

(Manual Position)

3.Once the engine starts, let it engine run for 1-2 minutes. Listen for any abnormal noises. If any abnormalities exists shutdown the engine and correct the problem. If the engine is running smoothly, place the engine speed switch (Figure 43) in the HIGH(up) position.

Figure 43. Engine Speed Switch (High)

4.Verify that the Engine Running status LED on the MPEC unit (Figure 44) is ON (lit) after the engine has been started.

Figure 39. Engine Enclosure Doors

Figure 44. Engine Running LED (ON)

 

PAGE 36 — DCA-100SSVU— OPERATION AND PARTS MANUAL — REV. #0 (11/05/07)