Starting (Auto Mode)
DANGER - ELECTRICAL SYSTEM HAZARDS
Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.
When starting generator in AUTO mode use the "Manual
1.Perform steps 1 through 5 in the Before Starting section.
2.Place the engine speed switch (Figure 54) in the HIGH position
CAUTION - BACKUP GENERATOR USE
When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.
Figure 54. Engine Speed Switch (High)
3.Place the MPEC Control Switch (Figure 55) in the AUTO position
When the generator is set in the AUTO mode, the generator will
NOTE automically start in the event of comercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.
Figure 55. MPEC Control Switch (AUTO)
4.Continue operating the generator as outlined in the Manual
WARNING - AUTO MODE MAINTENANCE
When running the generator in the AUTO mode, remember the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the auto mode.
CAUTION - ENGINE SPEED SWITCH
The Engine Speed Switch must be set to the “High” position when running in the