DCA-100SSVU — GENERATOR START-UP PROCEDURE (MANUAL)

5.The generator's frequency meter (Figure 45) should be displaying the 60 cycle output frequency in HERTZ.

9.The coolant temperature gauge (Figure 50) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 165~203 °F (74~95 °C), Green Zone.

Figure 50. Coolant

Temperature Gauge

Figure 45. Frequency Meter (Hz)

6.The generator's AC-voltmeter (Figure 47) will display the generator’s output in VOLTS. If the voltage is not within the specified tolerance, use the voltage adjustment control knob (Figure 47) to increase or decrease the desired voltage.

Figure 46. Voltmeter

Figure 47. Voltage Adjust Control Knob

7.The ammeter (Figure 48) will indicate zero amps with no load applied.When a load is applied, the ammeter will indicate the amount of current that the load is drawing from the generator.

Figure 48. Ammeter

(No Load)

10.Thetachometergauge(Figure51) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

Figure 51. Engine

Tachometer Gauge

11.Place the main, GFCI, and aux. circuit breakers in the ON position (Figure 52).

Figure 52. Main, Aux. and GFCI

Circuit Breakers (ON)

12.Observe the generator's ammeter (Figure 53) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.

8.The engine oil pressure gauge (Figure 49) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 44 to 73 psi. (303~503 kPa). When starting the genera

Figure 49. Oil

Pressure Gauge

13.The generator will run until manually stopped or an abnormal condition occurs.

DCA-100SSVU— OPERATION AND PARTS MANUAL — REV. #0 (11/05/07) — PAGE 37