Multiquip DCA-100SSVU— GENERATOR OUTPUTS, Voltage Selector Switch, Caution - Changingvoltages

Models: DCA-100SSVU

1 90
Download 90 pages 30.42 Kb
Page 28
Image 28
DCA-100SSVU — GENERATOR OUTPUTS

DCA-100SSVU — GENERATOR OUTPUTS

Voltage Selector Switch

The voltage selector switch (Figure 16) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Figure 16. Voltage Selector Switch

Voltage Selector Switch Locking Button

The voltage selector switch has a locking button to protect the generator and load from being switched while the engine is running. To lock the voltage selector switch, press and hold the red button located at the bottom of the switch.

CAUTION - CHANGINGVOLTAGES

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the open position before selecting voltage.

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage selector switch (Figure 16). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.

Table 7. Voltages Available

Three Phase

208V

220V

240V

416V

440V

480V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120V

127V

139V

240V

254V

277V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Generator Amperage

Table 8 describes the generator’s current output capability for both 1Ø-phase and 3Ø phase applications.

Table 8. Generator Maximum Amps

Model

DCA100SSVU

 

 

Rated Voltage

Maximum Amps

 

 

Single Phase

222.2 amps (4 wire)

120 Volt

 

 

 

Single Phase

111.1 amps (4 wire)

240 Volt

 

 

 

Three Phase

241 amps

240 Volt

 

 

 

Three Phase

120 amps

480 Volt

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly re- lated to the voltage being supplied at either the output termi- nals or the 2 twist lock auxiliary receptacles.

Tables 9 and 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the recep- tacles.

Table 9. 1Ø GFCI Receptacle Load Capability

KW in Use

Available Load

Twist-Lock (CS6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex NEMA

5-20R 120V

 

57.7

0

56.5

5 amps per receptacle

55.3

10 amps per receptacle

54.1

15 amps per receptacle

52.9

20 amps per receptacle

Table 10. 3Ø GFCI Receptacle Load Capability

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex NEMA

5-20R 120V

 

100

0

95.8

5 amps per receptacle

91.7

10 amps per receptacle

87.5

15 amps per receptacle

83.4

20 amps per receptacle

PAGE 28 — DCA-100SSVU— OPERATION AND PARTS MANUAL — REV. #0 (11/05/07)