DCA-25SSI — OUTPUT VOLTAGE SETUP

Voltage Selector Switch- 3 Phase 480/277V Position The following are additional voltages available when the voltage selector switch is in the 3 phase 480/277V position.

Single Phase: 480V, 440V, or 416 Volt

This setting can provide single phase power at 480, 440, or 416 volts. After hooking up the hard wires to the lugs as shown in Figure 21, 480 volts can be obtained the voltage regulator knob turned toward maximum; 440 volts can be obtained with the voltage regulator knob is turned down; and 416 volts can be obtained with the voltage regulator knob is at lowest setting.

Figure 19. Voltage Regulator Knob

3 Phase, 480V, 440V, or 416 Volt

This setting can provide 3-phase power at 480, 440, or 416 volts. After hooking up the hard wires to the lugs as shown in Figure 20, 480 volts can be obtained the voltage regulator knob turned toward maximum; 440 volts can be obtained with the voltage regulator knob is turned down; and 416 volts can be obtained with the voltage regulator knob is at lowest setting.

Figure 20. Hard Wire Hookup for Three Phase

480V, 440V, or 416V

Figure 21. Hard Wire Hookup for Single Phase 480V, 440V,

or 416V

Single Phase: 277V, 254V, or 240V

This setting can provide single phase power at 277, 254 or 240 volts. After hooking up the hard wires to the lugs as shown in Figure 22, 277 volts can be obtained the voltage regulator knob turned toward maximum; 254 volts can be obtained with the voltage regulator knob is turned down; and 240 volts can be obtained with the voltage regulator knob is at lowest setting.

Figure 22. Hard Wire Hookup for Single Phase 277V, 254V,

or 240V

PAGE 33 — DCA-25SSI — PARTS AND OPERATION MANUAL—FINAL COPY(06/29/01)

Page 33
Image 33
Multiquip DCA-25SSI operation manual Phase, 480V, 440V, or 416 Volt, Single Phase 277V, 254V, or