Multiquip GAC-9.7HZ manual installation, Connecting the Ground, Generator Grounding

Models: GAC-9.7HZ

1 88
Download 88 pages 8.18 Kb
Page 14
Image 14
installation

installation

Connecting the Ground

The nut and ground terminal on the generator should always be used to connect the generator to a suitable ground.The ground cable should be #8 size wire minimum.

At the generator, connect the terminal of the ground cable between the lock washer and the nut (Figure 2) and tighten the nut fully. Connect the other end of the ground cable to a suitable earth ground (ground rod).

Figure 2. Generator Grounding

page 14 — GAC9.7HZ 60 hz gENERATOR• operation and parts manual — rev. #2 (03/31/10)

Page 14
Image 14
Multiquip GAC-9.7HZ manual installation, Connecting the Ground, Generator Grounding