WI1501A 9/06 | Page 11 |
WIRING CONNECTIONS
BATTERY |
7 |
The RED (+) and BLACK
Wiring
TRANSFORMER
(The following applies to installations in the United States of America): Connect a 16.5 VAC Transformer to Terminals 1 and 2, using a wire of #18 AWG. or larger at a distance of 15 ft. or less from the control panel. NOTE: Do not connect to a switched outlet.
SIREN/BELL POWER | Connect the alarm sounding devices |
| speakers or a mechanical bell) to Terminals 3 and 4. Any self- |
| contained siren requiring a 12 VDC input can be connected. |
| When connecting a mechanical bell, it must be supervised |
| using a 2.2k Ohm resistor. To connect 8 Ohm Speakers use a |
| Siren Driver with the proper polarity observed. NOTE: Refer to |
| the |
| Note: In NFPA Household Fire Installations, only a single si- |
| ren or bell can be used on this bell circuit. |
AUXILIARY POWER
Connect the auxiliary devices (motion detectors, glass breaks, etc.) to Terminals 5 and 6. Auxiliary Power provides
Connections: Battery, Transformer, Siren Power, Aux. Power & PGM
PGM OUTPUTS (PGM1 & PGM2) |
PGM1 and PGM2 are negative switched programmable outputs that can be activated depending on the programming options selected (see
(+)and the PGM output
8. As an example, the connection to the RB1000 Relay Module is shown.
Outputs