Napco Security Technologies WI1501A Wiresmoke Detectors, Wir E S M O K E D E Te C To R W Ir In G

Models: WI1501A

1 44
Download 44 pages 7.1 Kb
Page 14
Image 14
4-WIRE SMOKE DETECTORS

Wiring Connections: 4-Wire Smoke Detectors & 2-Wire Smoke Detectors

Page 14

WI1501A 9/06

4-WIRE SMOKE DETECTORS

4-WIRE SMOKE DETECTOR WIRING

The F-64 Panel can use conventional 12 VDC 4-wire smoke detectors. To use them, select fire zone programming option and do not select 2-wire smoke detector programming option for the desired fire zone (refer to the F-64 Panel Programming Instructions). Set JP3 to the position as shown, if zones 7 or 8 are to be used.

Four wire smoke detectors may be connected to any programmed fire zone (1-8) as shown, within the panel. If the Zone Doubling is used (see EZ Zone Doubling Configuration), the respective complementary zones (9-16) are disabled when 4- wire smoke detectors are connected to zones 1-8. If external EZMs are used for zones 9-64, then 4-wire smoke detectors may be connected to any programmed fire zones (9-64).

Power must be obtained from terminal 25 and 6. If Fire Alarm Verification is desired to reset the smoke detectors, select this option for the desired fire zone.

2-WIRE SMOKE DETECTORS

2 -W IR E S M O K E

D E TE C TO R W IR IN G

Two-wire smoke detectors can only be connected to zones 7 and 8. To use them, select fire zone programming option and select 2-wire smoke detector programming option for the desired fire zone 7 or 8 (refer to the F-64 Panel Programming Instructions) and set JP3 to the “2-WF” position as shown. Connect the 2-wire smoke detectors as shown.

If the Zone Doubling is used (see EZ Zone Doubling Configuration), the respective complementary zones (15 & 16) are disabled when 2-wire smoke detectors are connected to zones 7 & 8.

If Fire Alarm Verification is desired to reset the smoke detectors, select this option for the desired fire zone (zone 7 or 8).

Freedom F-64 Installation Instructions

L NAPCO Security Systems

 

Page 14
Image 14
Napco Security Technologies WI1501A installation instructions Wiresmoke Detectors, Wir E S M O K E D E Te C To R W Ir In G