Napco Security Technologies Glossary, WI1501A 9/06, Page 31 , L NAPCO Security Systems

Models: WI1501A

1 44
Download 44 pages 7.1 Kb
Page 31
Image 31
Page 31 

WI1501A 9/06

Page 31 

Smoke Detectors; 2-Wire Smoke Detectors; Wireless Smoke Low Battery Resound

Connect smoke detectors as shown in the diagrams. The "Fire Power" (Terminal 25) is used to reset the smoke detectors.

Two-Wire Smoke Detectors

Two-wire smoke detectors may be used only on Zones 7 and 8. Up to 10 compatible 2-wire smoke detectors may be wired to each zone. In Residential applications, program Pulse Alarm Output. Zones 7 and 8 have been designed so they can be easily configured as 2-wire smoke detector zones by means of jumpers (JP3) located above Terminal 21.

1.Program Zones 7 and/or 8 for 2-Wire Smoke Detectors and Fire.

2.If Zone 7 is selected as a 2-Wire Fire Zone, move the left jumper on JP3 from the top two pins (BURG) to the bottom two pins (2WF).

3.Similarly, if Zone 8 is selected as a 2-Wire Fire Zone, move the right jumper on JP3 from the top two pins (BURG) to the bottom two pins (2WF).

4.Connect 2-wire smoke detectors to Zones 7 and/or 8 as shown earlier in this manual.

Four-Wire Smoke Detectors

If installing 4-wire smoke detectors, subtract smoke-detector alarm current from available standby current. See UL COMPATIBLE SMOKE DETECTORS on page 7.

Wire 4-wire smoke detectors as shown earlier in this manual. Program each zone for Fire. Also program zones for Pulse Alarm Output. If they are of the self-resetting type, 4-wire smoke detectors may be powered from Terminals 25 and 6.

Wireless Smoke Detectors

Wireless Smoke Low Battery Resound allows smoke detectors to sound off every 4 hours to indicate low battery voltage and the need for replacement. (Required for UL installations)

Sound Alarm On Exit Error

An Exit Error sequence is initiated if an entry/exit zone is violated at the expiration of the Exit Time. An Exit Error is processed as follows:

1.The local alarm shall immediately sound.

2.The Touchpad/keypad annunciator sounds an Entry Delay.

3.An Entry Delay is initiated.

4.If the alarm system is not Disarmed at the end of the Entry Delay, the Alarm Transmission Sequence is initiated.

5.The Alarm Transmission includes the alarm and an Exit Error Report Code.

Status Report See Closing Report

Subscriber ID Numbers (Account Number)

If reporting openings and/or closings, program Subscriber Opening/Closing Identification Numbers for each area for each telephone number used. If reporting events, program Subscriber ID Numbers for each area for each telephone number used. Subscriber ID numbers must be programmed for each area and telephone number, even if all are the same. Start with the left-most location.

Sum Check See Data Format

Suppress Bypass Icon When Armed

Enable this feature to inhibit the LCD window "BYPASS" display while armed.

Swinger Shutdown:

Swinger Shutdown is a common term used in the burglary alarm industry. It is a feature of an alarm panel that prevents multiple false alarms from being generated from faulty detectors (or wiring) by limiting the number of alarms a zone may report during a single arming period. NAPCO has this programmable-by-zone feature named Swinger Shutdown, and has been available on its panels for years. The SIA False Alarm Reduction standard CP-01 (to which the panel complies) requires the SIA definition of "swinger shutdown" on all non- fire zones. Our programmable feature allows three trips per arming period which is unacceptable in CP-01 installations. Therefore, to reduce confusion, the following defines both definitions of "Swinger Shutdown", namely (1) the NAPCO Programming Feature and (2) the CP-01 Requirement:

Swinger Shutdown (NAPCO Programming Feature): Program a zone with this feature to allow only three alarms per arming pe-

riod. Auto-Resetmust also be programmed for the zone for this feature to work. Enable 2 Count Swinger Shutdown: Same as Swinger Shutdown (NAPCO Programming Feature) above, but enables two alarms per arming period instead of three.

Swinger Shutdown (CP-01 Requirement): To meet CP-01, all non-fire zones must not be programmed for Auto-Reset. A zone not programmed for Auto-Reset will trip only one alarm per arming period. The panel leaves the factory with no zones programmed for Auto-Reset. If "Enable CP-01 Features" is selected in the Easy Menu Driven Program Mode, all non-fire zones will not be pro- grammed for Auto-Reset.

Glossary

L NAPCO Security Systems

Freedom F-64 Installation Instructions

 

Page 31
Image 31
Napco Security Technologies Glossary, WI1501A 9/06, Page 31 , L NAPCO Security Systems, Sound Alarm On Exit Error