WI1501A 9/06 | Page 5 |
SPECIFICATIONS
Freedom
Operating Temperature:
Input Power:
Loop Voltage:
Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm
Loop Resistance: 300 Ohm max.; 50 Ohm for
Alarm Voltage Output: 1
Programmable Negative Outputs: 2
Auxiliary Power Output:
Remote Power Output: 12 VDC regulated (for the
Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.
RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**
16.5VAC | BATTERY | STANDBY | ALARM | STANDBY |
TRANSFORMER | (12 VDC) | CURRENT | CURRENT | TIME |
|
|
|
|
|
40VA/50VA | 7 AH | 550 mA | 450 mA(1) | 4 Hours |
20VA* | 7 AH | 500 mA | 2.0 A | 4 Hours |
|
|
|
|
|
20VA* | 7 AH | 500 mA | 2.0 A | 6 Hours |
|
|
|
|
|
|
|
| ||
| COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY |
| ||
|
|
|
|
|
16.5VAC | BATTERY | STANDBY | ALARM | STANDBY |
TRANSFORMER | (12 VDC) | CURRENT | CURRENT | TIME |
|
|
|
|
|
40VA/50VA | 7 AH | 120 mA | 520 mA(1) | 24 Hours |
40VA/50VA * | Two 7 AH | 360 mA | 280 mA(1) | 24 Hours |
20VA * | 7 AH | 120 mA | 360 mA(1) | 24 Hours |
20VA * | Two 7 AH | 360 mA | 120 mA(1) | 24 Hours |
NOTE: (1) Alarm current can be increased by reducing standby current by the same amount.
*Not evaluated by UL.
**Commercial Burglary specifications not evaluated by UL.
FOR ALL UL INSTALLATIONS
"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED
The feature "Enable Residential Fire" (address 1422, option 4) must be programmed for ALL UL installations.
"DISABLE SYSTEM TROUBLE AUDIBLE TIMEOUT" (ADDRESS 2051) MUST BE PROGRAMMED The feature "Disable System Trouble Audible Timeout" (address 2051, option 7) must be programmed for ALL UL installations.
To program, please refer to the
EZM Module:
Keypad Current: See keypad Installation Instructions.
Maximum Number of Keypads / Touchpads: 7
Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads /
Touchpads and EZMs on run
Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)
Specifications