Napco Security Technologies WI1501A Specifications, For All Ul Installations

Models: WI1501A

1 44
Download 44 pages 7.1 Kb
Page 5
Image 5
SPECIFICATIONS

WI1501A 9/06

Page 5 

SPECIFICATIONS

Freedom F-64 Control Panel

Operating Temperature: 0-49°C(32-120°F)

Input Power: 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer

Loop Voltage: 10-13Vdc

Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm end-of-line resistor (Model EOL2.2K); 5mA for 2-wire smoke-detector zones; 1.4 mA using a 3.9K Ohm resistor (Model EOL3.9K) with Zone Doubling; 3mA with Se- ries Zone with Loop Supervision and 3mA with Series Zone Doubling with Loop Supervision

Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones

Alarm Voltage Output: 1

Programmable Negative Outputs: 2

Auxiliary Power Output: 11.7-12.5 VDC

Remote Power Output: 12 VDC regulated (for the F-64PROG programmer)

Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.

RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**

16.5VAC

BATTERY

STANDBY

ALARM

STANDBY

TRANSFORMER

(12 VDC)

CURRENT

CURRENT

TIME

 

 

 

 

 

40VA/50VA

7 AH

550 mA

450 mA(1)

4 Hours

20VA*

7 AH

500 mA

2.0 A

4 Hours

 

 

 

 

 

20VA*

7 AH

500 mA

2.0 A

6 Hours

 

 

 

 

 

 

 

 

 

COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY

 

 

 

 

 

 

16.5VAC

BATTERY

STANDBY

ALARM

STANDBY

TRANSFORMER

(12 VDC)

CURRENT

CURRENT

TIME

 

 

 

 

 

40VA/50VA

7 AH

120 mA

520 mA(1)

24 Hours

40VA/50VA *

Two 7 AH

360 mA

280 mA(1)

24 Hours

20VA *

7 AH

120 mA

360 mA(1)

24 Hours

20VA *

Two 7 AH

360 mA

120 mA(1)

24 Hours

NOTE: (1) Alarm current can be increased by reducing standby current by the same amount.

*Not evaluated by UL.

**Commercial Burglary specifications not evaluated by UL.

FOR ALL UL INSTALLATIONS

"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED

The feature "Enable Residential Fire" (address 1422, option 4) must be programmed for ALL UL installations.

"DISABLE SYSTEM TROUBLE AUDIBLE TIMEOUT" (ADDRESS 2051) MUST BE PROGRAMMED The feature "Disable System Trouble Audible Timeout" (address 2051, option 7) must be programmed for ALL UL installations.

To program, please refer to the F-64 Programming Instructions (WI1502) for further information.

EZM Module: GEM-EZM4/8: Input, 50mA

Keypad Current: See keypad Installation Instructions.

Maximum Number of Keypads / Touchpads: 7

Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads /

Touchpads and EZMs on run

Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)

Specifications

L NAPCO Security Systems

Freedom F-64 Installation Instructions

 

Page 5
Image 5
Napco Security Technologies WI1501A installation instructions Specifications, For All Ul Installations