2.3.1 Wiring Master/Slave Units via RS485 Interface

RS485 interface uses a two-wire communication system (one for transmitting and one for receiving) plus a common wire to connect to the shield of the cable. It is recommended to use a shielded cable with one twisted pair.

Use of twisted pair and shield will significantly improve noise immunity.

Figure 2.3 shows multi-point, half-duplex RS485 interface connections for the iServer.

Figure 2.2 Multi-point, Half-Duplex RS485 Wiring

Value of the termination resistor is not critical and depends on the cable impedance.

Table 2.3 shows RS485 half-duplex hookup between the iServer serial port and device with RS485 communication interface.

Table 2.3 Half Duplex Hookup

Pin#

iSeries

DEVICE # WITH RS485

Pin 9

+Tx/+Rx (+Transmit/+Receive)

+Tx/+Rx (+Transmit/+Receive)

Pin 10

-Tx/-Rx (-Transmit/-Receive)

-Tx/-Rx (-Transmit/-Receive)

Pin 8

RTN (Common GND)

GND (Common GND)