Wiring and Connecting the FLEXware Surge Protector

With the FW-SP-250 or FW-SP-ACA secured, connect all AC and DC wiring as well as any HUB,

MATE, AUX, and BATTERY TEMP cables.

Install all AC and DC power cables fi rst followed by the surge protector wires in their appropriate locations; each wire is labeled on the shrink-wrapped ends near the DC ring terminals and the AC spade lugs

If the AC cables are already installed, loosen the AC wiring block screws in order to insert the surge protector cables

Each surge protector wire inserts directly on top of any installed power wire with its label facing up. The surge protector spade lugs will sit on top of the AC wires connected to the wiring block. The surge protector ring terminals will sit on top of the FX’s DC lugs

Secure the AC wiring block screws to 22 inch-pounds and the DC cables to fi ve foot-pounds after installing each power cable and surge protector wire

MATE/HUB

Battery Temp

Figure 15: Securely connect the surge protector wires to the FX and connect any power, HUB, MATE, AUX, and/or BATTERY TEMP sensor wiring.

FLEXware Surge Protector Wiring Designations:

DC+

DC-

AC HOT OUT

AC HOT IN

AC NEUTRAL OUT

AC NEUTRAL IN

GROUND