CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

8 Operation Details

8.1.Basic Function

Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air temperature.

8.1.1.Internal Setting Temperature

Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes. These shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.

Table (a): Auto Operation Mode Setting

Mode Shift:

Temperature Shift (°C)

Cooling/Soft Dry Heating

-2.0

 

 

Heating Cooling/Soft Dry

+2.0

 

 

Table (b): Outdoor Air Temperature Shifting

Mode:

Outdoor Temperature, X (°C):

Temperature Shift (°C)

Cooling/Soft Dry

 

30

X

+0.5

 

 

X

30

+1.0

 

 

 

 

 

Heating

 

9

X

-1.0

 

 

 

 

 

 

5

X

9

-0.5

 

1

X

5

0.0

 

 

 

 

 

 

 

X

1

+1.0

Table (c): Powerful Mode Shifting

Mode:

Period, X (min):

Temperature Shift (°C)

Cooling

X

20

-2.0

 

X

20

0.0

 

 

 

 

Soft Dry

X

20

-1.0

 

X

20

0.0

 

 

 

 

Heating

X

20

+3.5

 

 

 

 

 

X

20

+3.5

16