CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

1. Relationship between the condition of the air conditioner and pressure and electric current

 

 

Cooling Mode

 

 

Heating Mode

 

Condition of the air

 

 

 

 

 

 

conditoner

Low Pressure

High Pressure

Electric current

Low Pressure

High Pressure

Electric current

 

 

 

during operation

 

 

during operation

 

 

 

 

 

 

 

Insufficient refrigerant

 

 

 

 

 

 

(gas leakage)

 

 

 

 

 

 

 

 

 

 

 

 

 

Clogged capillary tube

 

 

 

 

 

 

or Strainer

 

 

 

 

 

 

 

 

 

 

 

 

 

Short circuit in the

 

 

 

 

 

 

indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat radiation

 

 

 

 

 

 

deficiency of the

 

 

 

 

 

 

outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Inefficient compression

 

 

 

 

 

 

 

 

 

 

 

 

 

Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

12.2. Breakdown Self Diagnosis Function

Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below breakdown diagnosis method:

Press “CHECK” button at remote controller continuously for more than five seconds to turn on the diagnosis mode, “H11” will be displayed at remote controller.

By pressing the TMER “ ” button once, next error code will be displayed; press “V” button once, previous error code will be displayed.

If error code displayed matches the error code saved in unit memory (abnormality detected), “beep, beep, beep....” sounds will be heard for 4 seconds and Power LED will light on. Otherwise, one “beep” sound is heard.

If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off.

74