8.1.2.3.3.The frequency change method

1.When (suction-setup) remains in a domain for 30 seconds, after shifting to relative control, a tap is adjusted according to the domain and frequency changes relatively to the present condition.

2.A suction-setup is to other domains by load sudden change (remote control setting, open air introduction, etc.). When it moves, an addition-and-subtraction tap is changed from the time of the following renewal of data.

8.1.3.Cooling Operation8.1.3.1.Thermostat control

Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.

Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF point.