CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

D. Deodorizing Control

i. Control condition

Control at cooling/dry operation and auto fan speed.

No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.

ii. Operation

The odor status is arranged as below and it is shifted as follow.

* When COMP is ON

 

 

 

 

1 2 3

 

 

 

 

 

 

 

(Shift to 4 when COMP is OFF)

 

 

 

 

 

 

 

 

* When COMP is OFF

 

 

 

 

4 5 6 7 6 ←→ 7

 

 

 

 

(Shift to 1 when COMP is ON)

 

 

 

 

 

 

 

 

* Start from 4 if the Thermostat is OFF during the start operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Odor Status

1

2

3

 

4

5

6

 

7

6.7.6...

1

Status Shift

 

 

 

ON

 

 

 

OFF

 

 

ON

according to COMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status Shift

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

according

zone

40

50

 

30

90

20

 

90

20.90.20...

 

to time (s)

Dry zone

 

 

 

 

 

 

 

 

 

 

 

ON

 

Cooling

 

 

 

Auto Fan Speed

 

 

 

 

 

 

 

Fan Speed

zone

 

OFF

SSLo

 

 

SSLo

OFF

SSLo

OFF

SSLo.OFF...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry zone

 

 

 

SLo

 

 

 

 

 

 

 

 

8.1.8.Outdoor Fan Motor Operation

Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.

8.1.9.Airflow Direction

1.There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).

2.Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).

28