CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

13.2. Sensible Capacity Chart

CS-E9DKEW CU-E9DKE

230V

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

 

Indoor wet

 

30

 

 

35

 

 

40

 

 

46

 

bulb temp.

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

17.0°C

2.58

1.96

0.55

2.41

1.88

0.59

2.24

1.80

0.63

2.04

1.71

0.68

 

 

 

 

 

 

 

 

 

 

 

 

 

19.0°C

 

 

 

2.60

 

0.60

 

 

 

 

 

 

19.5°C

2.83

2.05

0.56

2.65

1.97

0.60

2.46

1.89

0.64

2.24

1.80

0.69

22.0°C

3.09

2.12

0.57

2.88

2.04

0.61

2.68

1.97

0.66

2.44

1.88

0.71

CS-E12DKEW CU-E12DKE

230V

 

 

 

 

 

Outdoor Temp. (°C)

 

 

 

 

 

Indoor wet

 

30

 

 

35

 

 

40

 

 

46

 

bulb temp.

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

TC

SHC

IP

17.0°C

3.47

2.63

0.88

3.24

2.52

0.95

3.02

2.43

1.02

2.74

2.30

1.10

 

 

 

 

 

 

 

 

 

 

 

 

 

19.0°C

 

 

 

3.50

 

0.97

 

 

 

 

 

 

19.5°C

3.81

2.76

0.90

3.56

2.65

0.97

3.31

2.55

1.04

3.01

2.43

1.12

 

 

 

 

 

 

 

 

 

 

 

 

 

22.0°C

4.15

2.86

0.92

3.88

2.75

0.99

3.61

2.65

1.05

3.28

2.53

1.14

82