CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

8.1.4.Soft Dry Operation8.1.4.1.Thermostat control

Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.

Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF point.

8.1.5.Heating Operation8.1.5.1.Thermostat control

Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C.

Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF point.

8.1.6.Automatic Operation

This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air temperature and outdoor air temperature.

During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.

23