CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

During heating operation, operate the followings control.

1.During Remote Control setting is 18°C & above

Indoor Fan Speed

Min Hz

More than Hi

27

 

 

More than Lo

27

Under Lo

27

 

 

However, when less than thermo OFF for 100 sec. continuously, the above control will be cancel.

8.2.1.11. DC Current Protection Control

Purpose

In order to control DC current rise in a compressor low frequency region, load is detected with from indoor/outdoor heat exchanger temperature, Hz control is performed.

Control contents

1. During cooling and dry except test mode

2.During heating compressor operation, except test mode. (However, official approval mode removes)

8.2.2.Protection Control For Cooling & Soft Dry Operation8.2.2.1.Outdoor Air Temperature Control

The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin one minute after the compressor starts.

38