CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the above operation mode chart, every 30 minutes.

Remote Control Setting Temperature (°C)

T1

T2

T3

16 ~ 18

+10

-3

-5

 

 

 

 

19 ~ 22

+8

-3

-7

23 ~ 26

+7

-3

-7

 

 

 

 

27 ~ 30

+6

-3

-8

There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice verse.

Operation Mode change from

Temperature shifts (°C)

Cooling/Soft Dry Heating

-2

Heating Cooling/Soft Dry

+2

 

 

Example of operation mode chart adjustment:

From the above table, if remote control setting temperature = 25,

T1 = 25 + 7 = 32; T2 = 25 - 3 = 22; T3 = 25 - 7 = 18

The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made.

8.1.7.Indoor Fan Motor OperationA. Basic Rotation Speed (rpm)

Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)

[Cooling, Dry, Fan]

Remote Control

O

O

O

O

O

Tab (rpm)

PSHI

SHI

Hi

Me+

Me

Me-

Lo

Lo-

SLo

SSLo

 

 

 

 

 

 

 

 

 

 

 

E9DK

1320

1320

1280

1165

1050

935

820

760

720

710

 

 

 

 

 

 

 

 

 

 

 

E12DK

1460

1460

1420

1293

1165

1038

910

840

720

710

[Heating]

Remote Control

O

O

O

O

O

Tab (rpm)

PSHi

SSHi

SHi

Me+

Me

Me-

Lo

Lo-

SLo

SSLo

E9DK

1440

1440

1400

1270

1140

1010

880

820

720

710

 

 

 

 

 

 

 

 

 

 

 

E12DK

1540

1540

1500

1395

1290

1185

1080

1010

720

710

24