A. Overheating Prevention Control
1.When the IPM temperature rises to 100°C, compressor operation will stop immediately.
2.Compressor operation restarts after three minutes the temperature decreases to 95°C.
B.DC Peak Current Control
1.When electric current to IPM exceeds set value of 18.5 A, the compressor will stop operate. Then, operation will restart after three minutes.
2.If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two minute.
3.If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
8.2.1.5.Compressor Overheating Prevention ControlInstructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below figure.
8.2.1.6.Low Pressure Prevention Control (Gas Leakage Detection)a. Control start conditionsControl will perform when (1) - (3) condition continues operation for 5 minute and (4) is fulfill.
1.During cooling and dry operation: Frequency more than normal Fcmax.
During heating operation: Frequency more than normal Fh
2.Outdoor total current I cooling: IbIIa
Heating: IbIIc Ic = Ia = 1.65 A Ib = 0.65 A
3.It is not during deice operation.
4.During cooling and dry operation: indoor
During of heating operation: Indoor piping
•compressor stops (restart after 3 minutes)
•if happen 2 times within (20 minutes), perform the following operation
1)Unit stop operation
2)Timer LED blink and “F91” indicated
36