CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

8.1.2.2.4.The frequency changed method

1.When intake-setting remains for 30 seconds in a domain after shifting to relative control, a tap is adjusted according to the domain and frequency changes relatively to the present condition.

2.A suction-setup to other domains by load sudden change (remote control setting change, open air introduction, etc.). When it moves, addition or subtraction tap is changed at the time of the following renewal of data.

3.When the load change was furthermore carried out and a suction-setup separates from the domain of relative control, it goes to the clause of initial frequency and operation frequency is determined.

8.1.2.3.The frequency determination method (Soft Dry operation control)8.1.2.3.1.Basic specification

The domain directions data (intake-setting) transmitted from indoor determines a changed part of frequency. Then, a directed changed part changes frequency to the present frequency.

Change of frequency may be 1 tap = 1Hz.

It applies to cooling correspondingly.

8.1.2.3.2.Initial frequency determination

It shifts to initial frequency after a starting frequency end.

 

ID intake 22°C

ID intake < 22°C

Frequency

ESCHZ02

ESCHZ01

 

 

 

 

38 (E12), 31 (E9)

34 (E12), 28 (E9)

21