ACTIVATE AUX

This setting activates an auxiliary when an alert condition exists. Settings include the following options:

NONE (default): Not activated.

1:An alert condition will close AUX 1.

2:An alert condition will close AUX 2.

CURRENT READING

The Current Reading menu displays the existing status of temperature, pressure, and dew point inside the dome system. An arrow displayed to the left of a menu item denotes that an alert condition exists.

CURRENT READING

TEMPERATURE

DEWPOINT

PRESSURE

REFRESH

BACK

EXIT

An up arrow indicates the reading is over the threshold. A down arrow indicates the reading is below the threshold.

The high temperature alert occurs if the temperature is above 140°F (60°C).

The low temperature alert occurs if the temperature is below –40°F (–40°C).

The high pressure alert occurs if the pressure is above 13 PSIG.

The low pressure alert occurs if the pressure is below 1 PSIG.

The dew point (high humidity) alert occurs if the difference between the temperature and the dew point is less than or equal to 3°C.

NOTE: The normal operating temperature inside the unit will be greater than the temperature outside the back box due to the heat emitted by the system’s electronics.

RESET ALERT

Reset alert clears the alert condition and removes the alert label from the monitor. The system automatically checks internal conditions 60 seconds after reset. If conditions are still unacceptable, the alert label reappears on the screen indicating further corrective action is required.