66
SunTouch Pool and Spa Control System Installation and Users Guide
Temp (Fo) Resistance (ΩΩ
ΩΩ
Ω) Temp (Fo) Resistance (ΩΩ
ΩΩ
Ω) Temp (Fo) Resistance (ΩΩ
ΩΩ
Ω)
-50 -58 669,500 25 77 10,000 95 203 787
-45 -49 471,500 27 80 9,298 96 205 761
-40 -40 336,200 29 85 8,250 99 210 701
-35 -31 242,500 30 86 8,056 100 212 679
-37 -35 280,100 32 90 7,331 102 215 646
-34 -30 234,100 35 95 6,530 104 220 596
-32 -25 196,300 38 100 5,826 105 221 587
-29 -20 165,100 40 104 5,326 107 225 552
-30 -22 176,800 41 105 5,209 110 230 510
-26 -15 139,300 43 110 4,663 113 235 472
-25 -13 130,300 45 113 4,367 115 239 444
-23 -10 118,000 46 115 4,182 116 240 438
-21 -5 100,200 49 120 3,757 120 248 389
-20 -4 97,000 50 122 3,602 125 257 341
-18 0 85,350 52 125 3,381 130 266 300
-15 5 72,910 54 130 3,047 135 275 264
-12 10 62,480 55 131 2,985 140 284 234
-9 15 53,640 57 135 2,750 145 293 208
-10 14 55,300 60 140 2,487 150 302 185
-7 20 46,230 63 145 2,251
-5 23 42,300 65 149 2,083
-4 25 39,910 66 150 2,041
-1 30 34,560 68 155 1,854
0 32 32,600 70 158 1,752
2 35 30,000 71 160 1,686
5 40 26,100 74 165 1,535
5 41 25,400 75 167 1,480
7 45 22,760 77 170 1,400
10 50 19,900 79 175 1,278
13 55 17,440 80 176 1,256
15 59 15,700 82 180 1,168
16 60 15,310 85 185 1,071
18 65 13,480 88 190 980

Temperature vs. Resistance Data

SunTouch systems use 10k Ω thermistor sensors. When the solar sensor is disconnected from the SunTouch

system, the sensor will read 10k Ω at 77º F (25ºC). Refer to the tables on the following pages for the

resistance at other temperatures. The resistance reading for any given temperature should be accurate to

±0.5ºF. For any given temperature, the resistance reading should be accurate to ±1%. Be sure that the solar

sensor is connected to the SunTouch system before making any DC voltage measurements. The reading should

be accurate to ± 2%.