Pentax N-0751M-OD installation manual For N-0751M, Vent Piping, Clearances, Appliance Adapters

Models: N-0751M-OD N-0751M

1 60
Download 60 pages 58.01 Kb
Page 13
Image 13
Vent Piping
Part No.
FSAA4
9401RYPK
2SVWA04
SRASPSA4

8. Vent Pipe Installation (Indoor Installation Only)

[ For N-0751M]

ClearancesAppliance Adapters WARNING

CARBON MONOXIDE POISONING

Follow all vent system requirements in accordance with relevant local or state regulation, or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI

Be sure to do

Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with NSCNGPI.

 

Vent Piping

Use only UL listed category III vent materials.

Follow the vent pipe manufacturer's installation instructions.

Pipe diameter

100mm (4")

 

 

No. of Elbows

Max. Straight Vent Length

3

4.6m (15')

2

8.2m (27')

1

11.7m (39')

Make the vertical section of the exhaust vent as short as possible.

Maintain the same vent pipe diameter from the heater flue to the vent termination.

Clearances

Manufacturer and

Enclosed

Unenclosed

 

 

 

 

 

 

Product

Hor.

Vert.

Hor.

Vert.

Noritz N-Vent

250mm (10") (sides)

100mm

75mm

75mm

150mm (6") (bottom)

(4")

(3")

(3")

 

 

375mm (15") (top)

 

 

 

 

Protech FasNSeal

200mm (8") (sides)

100mm

75mm

75mm

100mm (4") (bottom)

(4")

(3")

(3")

 

 

300mm (12") (top)

 

 

 

 

Protech FasNSeal W2

150mm

100mm

75mm

75mm

 

(6")

(4")

(3")

(3")

 

HeatFab SafTVent

150mm

150mm

50mm

50mm

(6")

(6")

(2")

(2")

 

Z-Flex Z-Vent

200mm

100mm

25mm

25mm

(8")

(4")

(1")

(1")

 

Flex-L-StaR-34

200mm

100mm

25mm

25mm

(8")

(4")

(1")

(1")

 

These clearances are subject to change.

Refer to the UL listing for the proper clearances.

The first vertical run from the top of the heater should be no longer than 0.9m (3').

Make sure vent pipe is gas tight and will not leak. Use silicon sealant wherever necessary.

Do not common vent or connect more than one appliance to this venting system.

The total vent length including horizontal & verti- cal vent runs should be no less than 0.9m (3').

Do not place any dangerous objects at the end of the exhaust vent and check that vent pipe is not blocked in any way.

Steam (smoke) or water drops may come out from the end of the exhaust pipe. Select the location for the end of the vent so that steam is not visible, and the vent is not wet with drip- ping water.

If snow is expected to accumulate, take care the end of the pipe is not covered with snow or hit by falling lumps of snow.

Consult the vent pipe manufacturer's install- ation instructions for chimney connections.

Appliance Adapters

Use the following adapters to connect the unit to the venting system.

Manufacturer and

Product

Protech FasNSeal

HeatFab SafTVent

Z-Flex Z-Vent

Flex-L Star-34

13

Page 13
Image 13
Pentax N-0751M-OD installation manual For N-0751M, Vent Piping, Clearances, Appliance Adapters