PB
CPP Monitor 2000 Users Manual
Datalogging
Number of Channels:
Inputs 1-8, AC Power & Nicad Battery backup (selectable)
Total Number of Samples: 32,768
Sampling Rate:
Programmable from 1 second to 200 hours
All samples include date and time.
Communication
Phone Line Connection:
RJ11 jack for connection to the public switched telephone network; pulse
& tone dialing
Communication Types:
Voice, Fax, E-mail, modem, alphanumeric pager, numeric pager
Dialing Parameters:
Calls up to 32 destinations (telephone numbers or E-mail addresses)
32 digit telephone numbers & 64 character E-mail addresses
Time between calls programmable from 10 seconds to 60 minutes
Maximum number of calling rounds programmable from 1 to 100
Programmable call list per input
Alarm acknowledgment via touch tones or callback
Call progress monitoring to detect dial tone, busy signals & ringback
Modem:
Data throughput 14,400 bps, 14,400 bps Fax
Protocols: V.32bis, V.32, V.22bis, V.22A/B, V.23, V.21, Bell 212A &103
Speech Technology:
(8) User-recorded voice alarm messages (4 seconds each) and (1)
Identification message (5 seconds); 53 seconds of pre-recorded
speech; 2.7KHz bandwidth, selectable speech for units of measure
Phone Line Surge Protection:
275V Metal Oxide Varistor