Appendix C: Engineering Specifications

APPENDIX C:

ENGINEERING SPECIFICATIONS

I.General

The Automatic dialer shall be a self-contained microprocessor controlled system capable of monitoring 10 alarm channels. The system shall be configured for operation by the user by means of the built-in keypad. The system shall have one alarm output. Characteristics of Input and Output channels include Dry Contact Input, 12V Run Time Input, 0-16V Analog Input, 10K Thermistor Input and 12VDC Output.

Upon detection of any alarm or status change, the system shall commence dialing telephone numbers from a list associated with the particular alarm condition(s). The alarm message shall be delivered in digitized human voice using messages recorded by the user. The system will continue to call telephone numbers in succession until a positive acknowledgment of the alarm message is received. Acknowledgment is accomplished by depressing tone keys from the called telephone, or by calling the system back within a programmed time period. The alarm may also be acknowledged by using the local keypad. In addition, the system shall be able to receive incoming telephone calls. Upon answering, the system shall recite a status report.

The system shall be FCC registered for direct connection to the telephone network. The system shall have a one year warranty from the manufacturer. The system shall be a Boat Remote by Phonetics, Inc.

II.I/O Channel Attributes and Features

A. Inputs

The system shall come standard with (2) Bilge Pump Inputs, (1) High Water Input, (3) Temperature Inputs, (1) Security Input, (1) Auxiliary Input and (1) 12V Battery Input.

The system shall have the following built-in monitoring features:

1.AC Power failure detection

2.Temperature with pre-wired 10K thermistor (-20F to 160F)

All monitored channels, including built-in monitoring features, shall