Installation
W A R N I N G
This UPS contains its own energy source (batteries). The output receptacles may carry live voltage even when the UPS is not connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground from the UPS and the equipment connected to the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
To comply with international standards, the sum of earth leakage current from the load connected to the UPS must not exceed 1 mA.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty.
Installing the Plug/Receptacle UPS
The following steps explain how to install the UPS. See •UPS Rear
Panels" on page 6 for the rear panel of each model.
1.If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
2.If installing an optional Extended Battery Module, plug the EBM cable into the battery connector on the EBM rear panel.
3.Plug the other end of the EBM cable into the battery connector on the UPS rear panel.
4.If additional EBMs are to be installed, plug the EBM cable of the second cabinet into the battery connector on the first EBM. Repeat for each additional EBM.
5.On 208V or 230V models, plug the power cord into the input connector on the UPS rear panel.
6.Plug the UPS power cord into a power outlet. The fan turns on and the UPS enters Standby mode.