Installation
6.Remove the terminal block cover and the wiring knockouts (see Figure 2). Retain the terminal block cover.
USB Port | Communication Slot | |
Communication Port | Network | |
Transient | ||
| ||
| Protector | |
| Battery | |
| Connector | |
| REPO Port | |
Fans |
| |
| Panel Cover Screws |
Output Wiring
Access KnockoutTerminal Block
Cover
Input Wiring
Access Knockout
Panel Cover Screws
Figure 2. 3000 VA, 120V Hardwired Rear Panel
7.Pull the input wires through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach a flexible metal fitting to the end of the conduit.
8.Insert the conduit through the input wiring access knockout and attach the conduit fitting to the panel. Strip 0.5 (1.5 cm) of insulation from the end of each incoming wire.
9.Connect the input and ground wires to the input terminal block (see Figure 3).
10.Pull the output wires through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach a flexible metal fitting to the end of the conduit.
11.Insert the conduit through the output wiring access knockout and attach the conduit fitting to the panel. Strip 0.5 (1.5 cm) of insulation from the end of each incoming wire.