Additional UPS Features
Use the following procedure to install the REPO switch:
1.Verify that the UPS is off and unplugged or removed from utility power.
2.Unscrew and remove the REPO connector from the mating plug on the UPS rear panel.
3.Remove the short wire from the REPO connector.
4.Connect isolated, normallyclosed, dry contacts (rated at 60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum) across the REPO device to Pin 1 and Pin 2 (see
Figure 6). Use stranded, nonshielded wiring, size 1822 AWG (0.75 mm20 mm2). See Figure 7.
Pin 1 | Pin 2 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 6. REPO Connector
|
|
|
|
| Normally Closed, |
REPO Connector | Isolated Switch | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Powerware 9120 UPS
Figure 7. REPO Wiring Diagram
5.Reconnect the REPO connector to the REPO port on the UPS rear panel.
6.Verify that the
7.Connect the UPS to a power source.
22 | Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy |