Configuration
Parameter | LCD Message | Description | Default Settings | ||
|
|
|
|
|
|
Number of | Bat Pack Num Set | Select the number of EBMs connected to the UPS: | Extern Pack: 0 | ||
Extended Battery |
| For 7001500 VA models, select 0 through 2. |
| ||
Modules |
| For 20003000 VA models, select 0 through 5. |
| ||
|
| You are prompted to save this setting. |
| ||
|
|
|
|
|
|
Communications | COM Control Cmds | For greater levels of security, users may choose to | Enable | ||
| have the UPS disregard shutdown commands that |
| |||
|
| come from the power management software or other |
| ||
|
| communication sources. |
| ||
|
| When disabled, the UPS does not accept a shut |
| ||
|
| down command via the communication port, USB |
| ||
|
| port, or communication slot adapter. |
| ||
|
| When enabled, the UPS operates normally in |
| ||
|
| response to external commands. |
| ||
|
| You are prompted to save this setting. |
| ||
|
|
|
| ||
Load Segment | Load Group Set | Allows manual control of load segments (see •Load | Group 1On 2On | ||
Control |
| Segments" on page 24). |
| ||
|
| By repeatedly pressing the scroll button, the individual |
| ||
|
| load segments can be turned on and off. |
| ||
|
| CAUTION To prevent the unintentional shutdown of |
| ||
|
| specific load segments, confirm your selection before |
| ||
|
| pressing the |
| button. |
|
|
|
|
| ||
|
|
|
| ||
Manual Bypass | Manual Bypass GO | This parameter is used to manually place the UPS in | Bypass OFF | ||
|
| Bypass mode. |
| ||
|
|
|
| ||
Configuration Mode | Config Mode Set | This parameter is reserved for future use, and should | EscapeConfigMode | ||
Setting |
| not be modified by the user. The setting may be |
| ||
|
| toggled between EscapeConfigMode and Enter |
| ||
|
| ConfigMode. It should always be set to |
| ||
|
| EscapeConfigMode. |
| ||
|
|
|
|
|
|
20 | Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy |