Configuration

Parameter

LCD Message

Description

Default Settings

 

 

 

 

High-Efficiency

HE Mode Setting

Select whether High-Efficiency mode is On or Off. If

HE Mode Off

Mode

 

enabled, you must also select the input voltage range:

 

 

 

±10% or ±15%.

 

 

 

While operating in High-Efficiency mode, the UPS

 

 

 

transfers to utility power when: 1) the input voltage is

 

 

 

outside ±10% or ±15% from nominal; 2) the input

 

 

 

frequency is greater than ±3%; or 3) the input line is

 

 

 

not available.

 

 

 

You are prompted to save this setting.

 

 

 

 

 

Free Run Mode

Free Run Mode

Select whether Free Run mode is On or Off. If enabled,

 

 

you must also select Bypass Disable or Bypass Enable.

 

 

This selection defines how your UPS runs when the

 

 

input frequency (from the utility) is outside the

 

 

selected frequency tolerance (set via the I/P F Setting,

 

 

above), but is inside the maximum frequency limits the

 

 

UPS can accept before switching to Battery mode.

 

 

For example: If your 60 Hz UPS is set to the factory

 

 

default window of ±5% before the UPS starts

 

 

regulating the frequency:

 

 

￿ The output frequency tracks the input frequency

 

 

exactly from 57 to 63 Hz.

 

 

￿ If input frequency is between 45 and 57 Hz, or

 

 

between 63 and 65 Hz, the output frequency is

 

 

regulated by the UPS to exactly 60 Hz (±0.5 Hz).

 

 

You are prompted to save this setting.

Free Run On (Bypass Disable)

Alarm Silence

Alarm Silence

Select whether Silence is On or Off. If enabled, the

Silence Off

 

 

UPS silences the alarm for an existing fault. If the UPS

 

 

 

status changes, the alarm beeps, overriding the

 

 

 

previous alarm silencing. The alarm does not silence if

 

 

 

there is a low battery condition.

 

 

 

 

 

 

 

 

 

 

 

Manual Battery

Manual Bat Test

To initiate a manual battery test, press the

 

 

 

button

Battery Test

 

Test

 

twice. During the test, the LCD displays On BATTERY.

 

 

 

The UPS resets the automatic timer after a manual

 

 

 

battery test.

 

 

 

 

 

 

 

 

 

Manual UPS Test

Manual UPS Test

To initiate a manual UPS self-test, press the

 

button

UPS Test

 

 

 

 

twice. During the test, the LCD displays On BATTERY.

 

 

 

 

 

Site Wiring Fault

Site Fault Set

Select Enable or Disable. When enabled, the alarm

Detect Enable

Alarm

 

sounds when the ground connection is missing or the

 

 

 

line and neutral wires are reversed in the wall outlet.

 

 

 

 

 

Modem Support

Modem Support

This parameter is reserved for future use, and should

No Modem Support

 

 

not be modified by the user.

 

 

 

 

 

 

 

 

 

 

 