Configuration
5.To exit Configuration mode at any time, do not press any buttons for five seconds. The UPS returns to Normal mode and displays On Line.
LCD Panel
Press the Scroll button to enter Configuration mode. Also press to scroll to the next option.
Press the Enter button to select a parameter. Also press the Enter button to select an option and to save the setting.
Figure 5. Using the Configuration Mode
Table 1. Configuration Mode Parameters
Parameter | LCD Message | Description | Default Settings |
|
|
|
|
Output Voltage | O/P V Setting | To change the output voltage: | For 120V models: |
Setting |
| Select 100, 110, 120, or 127V for 120V models. | O/P V= 120V |
Select 200, 208, 220, 230, or 240V for 208V models. For 208V models:
|
| Select 208, 220, 230, or 240V for 230V models. | O/P V= 208V |
|
| You are prompted to save this setting. | For 230V models: |
|
|
| O/P V= 230V |
|
|
|
|
Input Voltage | I/P Bypass Set | Select the input voltage tolerance range before the | I/P |
Tolerance |
| UPS goes to Battery mode: ±10%, |
|
|
|
| |
|
| You are prompted to save this setting. |
|
|
|
|
|
Input Voltage | I/P F Setting | The | Freq |
Frequency |
| for a narrower frequency range. Select ±7% for a |
|
|
| wider frequency range. |
|
|
| You are prompted to save this setting. |
|
|
|
|
|
18 | Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy |