Troubleshooting
LCD Message or | Possible Cause | Action |
Condition |
|
|
|
|
|
Battery Overload | The UPS is on battery, and the | Shutdown is imminent (30 seconds). Save your work and |
2 beeps per second. | power requirements exceed | turn off your equipment. Turn off and unplug or remove |
| UPS capacity (130% for | utility power from the UPS. Remove some of the equipment |
| 10 seconds or >130% for | from the UPS. Restart the UPS. You may need to obtain a |
| 1.5 seconds) or the load is | larger capacity UPS. |
| defective. |
|
|
|
|
Site Fault
1 beep per second.
Ground wire connection does not exist or the line and neutral wires are reversed in the wall outlet.
Have a qualified electrician correct the wiring.
To disable this alarm, see •Configuration Mode" on page 17.
Battery Test | The UPS is performing a battery |
| test. |
None. The UPS returns to Normal mode when it completes a successful battery test.
UPS internal temperature is too | |
Constant beep. | high. |
Shutdown is imminent. Save your work and turn off your equipment. Turn off the UPS.
Clear vents and remove any heat sources. Ensure the airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact your service representative.
Batteries are | |
Constant beep. |
|
Save your work and turn off your equipment. Turn off the UPS. Contact your service representative.
Charger Failure | Charger has failed. | Save your work and turn off your equipment. Turn off the |
|
| UPS. Contact your service representative. |
|
|
|
Output Short | Output short circuit. | Save your work and turn off your equipment. Turn off the |
Constant beep. |
| UPS. Contact your service representative. |
|
|
|
High Output Voltage | High output voltage. | Save your work and turn off your equipment. Turn off the |
Constant beep. |
| UPS. Contact your service representative. |
|
|
|
Low Output Voltage | Low output voltage. | Save your work and turn off your equipment. Turn off the |
Constant beep. |
| UPS. Contact your service representative. |
|
|
|
High DC Bus | High internal DC bus voltage. |
2 beeps per second. |
|
Save your work and turn off your equipment. Turn off the UPS. Contact your service representative.
Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy | 39 |