Additional UPS Features

Relay Card

This interface provides true relay contact output to peripheral devices. Outputs are user-selectable as normally open or normally closed.

Table 3. Relay Card (AS/400) Pin Assignment

Pin Number

Signal Name

Definition

Direction

 

 

 

 

1

UPS Fail

Relay contact; normally open, closes

Out

 

 

when UPS fails.

 

 

 

 

 

2

Summary Alarm

Relay contact; normally open, closes

Out

 

 

when UPS fails, bypass is activated,

 

 

 

utility power failure, or low battery

 

 

 

status.

 

 

 

 

 

3

Remote Shutdown (-)

Ground

￿

 

 

 

 

4

Remote Shutdown (+)

Activated by +5 to +12V for one second

In

 

 

 

 

5

Common

Relay common connection for pins 1, 2,

￿

 

 

6, 7, 8, and 9.

 

 

 

 

 

6

Bypass

Relay contact; normally open, closes

Out

 

 

when the UPS is in Bypass mode.

 

 

 

 

 

7

Low Batt

Low Battery relay contact; normally

Out

 

 

open, closes when the battery is almost

 

 

 

discharged.

 

 

 

 

 

8

Battery Mode

Activated by +5 to +12V for one second.

In

 

Remote Shutdown

 

 

 

 

 

 

9

AC Fail

AC Fail relay contact; normally open,

Out

 

 

closes when utility power fails.

 

 

 

 

 