Operation
Display Mode
To view the UPS current settings, press the button for one second. Use the button to scroll through the list of settings:
LCD Message | Description |
|
|
I/P VOLT= xxx.xV | Input voltage. |
|
|
I/P FREQ= xx.xHZ | Input frequency. |
|
|
O/P VOLT= xxx.xV | Output voltage. |
|
|
O/P FREQ= xx.xHZ | Output frequency. |
|
|
O/P Load = x% | Approximate percentage of UPS load capacity being used by the |
| protected equipment. |
|
|
O/P Watt= xW | Output watts. |
|
|
O/P VA= xVA | Output VA. |
|
|
O/P Cur= x.xA | Output current. |
|
|
BAT VOLT= xx.xV | Battery voltage. |
|
|
BAT CHARGE= xxx% | Approximate percentage of battery capacity remaining. |
|
|
BackUp Time= xxxM | Approximate battery time remaining in minutes. The display changes |
| to seconds after one minute (Backup Time= xxxS). |
|
|
CPU Version x.xx | Firmware revision level. |
|
|
NOTE The UPS exits Display mode automatically after five seconds if the button is not pressed.
Turning the UPS On
After the UPS is connected to a power source, the fan turns on and the UPS enters Standby mode. To turn on the UPS, press and hold the button until you hear the UPS beep (approximately one second). The LCD briefly displays On Delay and the indicator illuminates. Then the UPS conducts a selftest, briefly displaying On BATTERY. If an alarm condition occurs, see Table 10 on page 37.
When the
14 | Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy |