Troubleshooting
LCD Message or | Possible Cause | Action |
| ||
Condition |
|
|
|
| |
|
|
|
| ||
LCD panel is blank. | The UPS is in Standby mode. | Press and hold the | button until your hear the UPS beep | ||
|
|
| (approximately one second). | ||
|
|
| |||
| The LCD has failed. | Contact your service representative. | |||
|
|
| |||
UPS does not provide the | The battery may be fully | Connect the UPS to a power source for 24 hours to charge | |||
expected backup time. | discharged because of: | the battery. Perform a battery test (see •Configuration | |||
| Mode" one page 17). If the battery test fails, see •Replacing | ||||
| frequent power outages | Batteries" on page 29 to replace the battery. | |||
| end of battery life | During extended power outages, save your work and turn off | |||
| your equipment to conserve battery power. | ||||
|
|
| |||
|
|
| |||
The UPS operates | The equipment is not connected | Verify that the equipment is properly connected to the UPS. | |||
normally, but some or all | to the UPS. |
|
| ||
of the protected |
|
|
|
| |
The output circuit breaker (if | Reset the circuit breaker (push the circuit breaker button or | ||||
equipment is not on. | |||||
| applicable) is open. | reset the switch). |
| ||
|
|
| |||
| One of the load segments has | Reactivate the segment with the power management | |||
| been turned off. | software or through the front panel (see •Configuration | |||
|
|
| Mode" one page 17). |
| |
|
|
| |||
Utility power failure. | The UPS is powering your equipment with its internal | ||||
1 beep every 5 seconds. |
|
| battery. If this is an extended power outage, save your work | ||
|
|
| and turn off your equipment to conserve battery power. | ||
|
|
|
|
|
Low Battery | The battery is running low. |
2 beeps every 5 seconds. |
|
2 minutes or less of battery power remains (depending on load and battery charge).
Prepare for a shutdown. Save your work and turn off your equipment. The alarm cannot be silenced.
Replace Battery | The battery needs replacing. | See •Replacing Batteries" on page 29 to replace the battery. |
3 beeps every 5 seconds. |
|
|
|
|
|
Low Charge | The battery voltage is low. |
3 beeps every 5 minutes. |
|
The UPS is charging the batteries and may not deliver full run time. The alarm continues until at least two minutes of run time is available.
Output Overload
2 beeps per second.
Power requirements exceed UPS capacity (110125% for 1 minute or 126150% for 10 seconds) or the load is defective. The UPS switches to Bypass mode.
Remove some of the equipment from the UPS. The UPS automatically switches back to Normal mode when the capacity returns to an acceptable level. You may need to obtain a larger capacity UPS.
38 | Powerware® 9120 User's Guide 05147426 A Uncontrolled Copy |