Specifications

Table 8. Battery

Configuration

700 VA: (2) 12V, 7 Ah internal batteries; 24 Vdc

 

1000 VA: (3) 12V, 7 Ah internal batteries; 36 Vdc

 

1500 VA: (4) 12V, 7 Ah internal batteries; 48 Vdc

 

2000￿3000 VA: (8) 12V, 7 Ah internal batteries; 96 Vdc

 

 

 

EBM Configuration

PW9120 BAT-700:

(4) 12V, 2￿7 Ah; 24 Vdc

 

PW9120 BAT-1000:

(6) 12V, 2￿7 Ah; 36 Vdc

 

PW9120 BAT-1500:

(8) 12V, 2￿7 Ah; 48 Vdc

 

PW9120 BAT-3000:

(16) 12V, 2￿7 Ah; 96 Vdc

 

 

Type

Sealed, maintenance￿free, valve￿regulated, lead￿acid

 

 

Charging

Approximately 4 hours to 90% usable capacity at nominal line voltage after full load discharge

 

 

 

Table 9. Battery Run Times (in Minutes)

 

 

Run Times at Full/Half Load by UPS VA Ratings

 

Number of Batteries

 

 

 

 

 

700 VA

1000 VA

1500 VA

2000 VA

3000 VA

 

 

 

 

 

 

 

UPS Internal Batteries

7/18

7/18

7/18

12/34

6/15

 

 

 

 

 

 

1 EBM

34/70

36/80

29/67

49/107

30/70

 

 

 

 

 

 

2 EBMs

64/140

66/155

56/130

93/195

58/128

 

 

 

 

 

 

3 EBMs

 

 

 

141/310

87/191

 

 

 

 

 

 

4 EBMs

 

 

 

192/403

120/264

 

 

 

 

 

 

5 EBMs

 

 

 

240/504

148/325

 

 

 

 

 

 

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.