Installation
12.Connect the output and ground wires to the output terminal block (see Figure 3).
Line
Ground
Neutral
Line
Ground
Neutral
L
OUTPUT
N
L
INPUT
N
Output Connections
Input Connections
Figure 3. Terminal Block
13.Replace the terminal block cover.
14.Switch the main utility breaker on.
15.To start the UPS, press and hold the button until you hear the UPS beep (approximately one second). The LCD briefly displays On Delay and the indicator illuminates. Then the UPS conducts a selftest, briefly displaying On BATTERY. If an alarm condition occurs, see Table 10 on page 37.
When the
16.If you installed optional EBMs, configure the number of EBMs through the front panel so that the UPS can estimate the available battery run time (see •Configuration Mode" on page 17).
NOTE The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 6 to 24 hours after installation or