Powerware 9335 operation manual To Operate a Remote EPO, Remote EPO Wire Terminations

Models: 9335

1 100
Download 100 pages 43.22 Kb
Page 28
Image 28

Table 4 – 1. Remote EPO Wire Terminations

From Remote

To X1 connector on front

Remarks

EPO Switch(s)

of inner UPS panel

 

Refer to switch

X1 - 1

Twisted

manufacturers

wires (2) 14-

 

installation

X1 - 2

18 gauge

instructions

 

 

 

Table 4 – 2. Remote EPO

REMOTE

EPO

SWITCH

(N.C.)

TWISTED WIRES (2)

X1 UPS

Remote EPO switch rating is 24 VDC, 1 Amp maximum

NOTE: This switch must be a dedicated switch not tied into any other circuits.

4.If you are installing multiple Remote EPO stations, wire additional stations in series with the first Remote EPO.

5.If required, install appropriate sized conduit and wiring from the Remote EPO switch to trip circuitry of upstream protective devices. A separate contact block, with the appropriate normally open or normally closed contacts, must be used for this function. Remote EPO switch wiring must be in accordance with UL Class 1 requirements.

6.Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation.

4.3To Operate a Remote EPO:

1.Activation of an EPO switch will interrupt the EPO circuit and immediately shut off UPS main circuit power to the load, as well as the DC input from the battery supply.

2. Even though the EPO switch is opened, the UPS will not re-energize until the normal startup procedure is followed, which requires operator intervention at the UPS cabinet controls.

4-2

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103

Page 28
Image 28
Powerware 9335 operation manual To Operate a Remote EPO, Remote EPO Wire Terminations