2.If the loads are all disconnected, press simultaneously the two ON/OFF buttons on the UPS control panel. On the LCD Display, “LOAD OFF, SUPPLY FAILURE” will appear and the LED-indicator will indicate as shown below:

LED Indicator

Color

LINE 1

Green

LINE 2

OFF

BYPASS

OFF

INVERTER

OFF

BATTERY

Flashing Green

3.Rotate the Parallel Isolator Switch (IA2) to the “O” (OFF) position.

4.Open battery cabinet breakers in external battery cabinets or racks.

5.Open the input utility supply circuit breakers, if used.

THE POWERWARE 9335 IS NOW VOLTAGE FREE.

8.4 Load Transfer to Maintenance Bypass

If it is necessary to perform service or maintenance on the UPS, it is possible to transfer the UPS to MAINTENANCE BYPASS.

CAUTION:

BEFORE YOU ROTATE THE MAINTENANCE BYPASS SWITCH TO POSITION “I” (ON ), MAKE SURE THAT THE LOAD HAS BEEN TRANSFERRED TO THE BYPASS MODE. EVEN THOUGH THE UNIT IS IN BYPASS MODE, LETHAL VOLTAGE IS STILL PRESENT WITHIN THE UPS CABINET.

CAUTION:

ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORIZED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.

Status of the UPS-System before starting the Transfer Procedure to Maintenance Bypass

The load is protected by the Powerware 9335 UPS system in normal operation (the UPS is operating on inverter).

1)Load transfer to Maintenance Bypass

Go to Menu COMMANDS and choose command “LOAD TO BYPASS” and transfer the load to utility supply on control panel of the UPS cabinet.

On the LCD Display: “LOAD NOT PROTECTED” will appear.

8-4

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103

Page 64
Image 64
Powerware 9335 operation manual Load Transfer to Maintenance Bypass, Line OFF Bypass Inverter Battery

9335 specifications

The Powerware 9335 is a robust and efficient uninterruptible power supply (UPS) designed to deliver reliable power protection for critical applications. Expanding upon Eaton's tradition of offering advanced power management solutions, the Powerware 9335 is tailored for environments that demand high availability and uptime.

One of the standout features of the Powerware 9335 is its double-conversion online topology, which ensures a continuous supply of clean and regulated power. This design operates without any transfer time to battery power, effectively protecting sensitive equipment from all types of power disturbances, including surges, sags, and outages.

The UPS is available in a range of power ratings, from 8 kVA to 40 kVA, making it versatile enough to support a variety of applications ranging from small server rooms to larger data centers. The modular architecture of the Powerware 9335 allows for seamless scalability, enabling users to add additional capacity or redundancy as their power needs evolve. This feature is particularly beneficial in dynamic environments where equipment and loads can frequently change.

Another significant characteristic of the Powerware 9335 is its high efficiency, often exceeding 94% in normal operation. This efficiency not only reduces energy costs but also minimizes heat generation, leading to lower cooling requirements. The UPS employs advanced technologies such as Intelligent Power Management and Smart APM (Adaptive Power Management) to optimize power usage, further enhancing its overall performance and reducing the total cost of ownership.

The user-friendly LCD display furnishes real-time data regarding UPS status, battery condition, and power settings, facilitating proactive management and monitoring. In addition, the unit can be monitored and managed remotely, ensuring that administrators can access critical information even when they are not on-site.

The Powerware 9335 also comes equipped with various connectivity options, including USB, serial, and SNMP for seamless integration into existing IT infrastructure. Additionally, advanced communication capabilities allow for integration with building management systems, ensuring comprehensive power management and reporting.

Safety is paramount, and the Powerware 9335 incorporates numerous features designed to protect both the UPS and connected equipment. This includes overload protection, battery health monitoring, and environmental monitoring, which collectively contribute to a resilient power protection strategy.

In summary, the Powerware 9335 is an exceptional UPS offering from Eaton, featuring high availability, scalability, efficiency, and robust management options. With its advanced technologies and features, it stands out as a premier choice for organizations seeking to safeguard their critical systems and data.