LED Indicator | Color |
LINE 1 | Green |
LINE 2 | Green |
BYPASS | Green |
INVERTER | OFF |
BATTERY | Flashing Green |
6.If necessary, perform Command: LOAD TO INVERTER (see sections 7.3.2 and 7.3.6) On LCD Display, “LOAD PROTECTED” will appear and the
LED Indicator | Color |
LINE 1 | Green |
LINE 2 | Green |
BYPASS | OFF |
INVERTER | Green |
BATTERY | Flashing Green |
7.Close the external battery cabinet circuit breaker.
8.Scroll through the measurements menu and verify that battery polarity and voltage are proper and within prescribed limits (see sections 7.3.2 and 7.3.5). For the
80 kVA model, the voltages will be about +260 and
9.Close Parallel Isolator Switch (IA2) to position “I” (ON). UPS power is now present on the output terminal block and “LOAD PROTECTED” will appear on the LCD display. After
On initial
10.Perform load transfer to Maintenance Bypass
•Use Menu COMMANDS on UPS control panel and choose “LOAD TO BYPASS” (see sections 7.3.2 and 7.3.6) to transfer the load to the bypass source.
•Close Maintenance Bypass Switch (IA1) to position “I” (ON). The LCD display will show “MANUAL BYP. CLOSED” and the LED indicators will appear as follows:
LED Indicator | Color |
LINE 1 | Green |
LINE 2 | Green |
BYPASS | Green |
INVERTER | Red |
BATTERY | Green |
11.Connect load to the UPS output
•Close external output circuit breakers in the load distribution panel
•Verify on the LCD Display and LED indicators that the load is on Bypass.
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation | |
| 164201396 REV A 071103 |