Powerware 9335 operation manual LED Indicator Color

Models: 9335

1 100
Download 100 pages 43.22 Kb
Page 62
Image 62

LED Indicator

Color

LINE 1

Green

LINE 2

Green

BYPASS

Green

INVERTER

OFF

BATTERY

Flashing Green

6.If necessary, perform Command: LOAD TO INVERTER (see sections 7.3.2 and 7.3.6) On LCD Display, “LOAD PROTECTED” will appear and the LED-indicators will display as follows:

LED Indicator

Color

LINE 1

Green

LINE 2

Green

BYPASS

OFF

INVERTER

Green

BATTERY

Flashing Green

7.Close the external battery cabinet circuit breaker.

8.Scroll through the measurements menu and verify that battery polarity and voltage are proper and within prescribed limits (see sections 7.3.2 and 7.3.5). For the

80 kVA model, the voltages will be about +260 and –260. For the 120 kVA model, the voltages will about +312 and –312 volts.

9.Close Parallel Isolator Switch (IA2) to position “I” (ON). UPS power is now present on the output terminal block and “LOAD PROTECTED” will appear on the LCD display. After 45-120 seconds, the battery LED will change from Flashing Green to Solid Green. This state change will take up to one minute.

On initial start-up follow steps 9-14. On re-start stop at 9.

10.Perform load transfer to Maintenance Bypass

Use Menu COMMANDS on UPS control panel and choose “LOAD TO BYPASS” (see sections 7.3.2 and 7.3.6) to transfer the load to the bypass source.

Close Maintenance Bypass Switch (IA1) to position “I” (ON). The LCD display will show “MANUAL BYP. CLOSED” and the LED indicators will appear as follows:

LED Indicator

Color

LINE 1

Green

LINE 2

Green

BYPASS

Green

INVERTER

Red

BATTERY

Green

11.Connect load to the UPS output

Close external output circuit breakers in the load distribution panel

Verify on the LCD Display and LED indicators that the load is on Bypass.

8-2

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103