Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9335 – 80 kVA
| Ratings | Units | Rating 50/60 Hz |
Basic unit ratings at | kVA | 80 | |
0.8 lagging PF load | W |
| |
|
| INPUT/ OUTPUT | 480 |
|
| VOLTAGE |
|
AC | AC Input to UPS Rectifier (0.95 min. PF) | Amps* | 105 |
3 phase, 1 neutral, 1 ground |
|
| |
INPUT | Minimum conductor size *Max. amps | AWG or kcmil (ea) | 1/0 |
A | include full load current plus |
|
|
battery recharge current |
|
| |
| AC Input to UPS Bypass - Full Load | Amps* | 97 |
AC | Current 3 phase, 1 neutral, 1 ground |
|
|
INPUT | Minimum conductor size | AWG or kcmil (ea) | 1/0 |
B |
|
|
|
| DC Input from Ext. Battery source to | VDC (nominal) | +240 0 |
DC | UPS | Amps* | 167 |
INPUT | (1) positive, (1) negative, (1) |
|
|
C | Minimum conductor size | AWG or kcmil (ea) | 4/0 |
|
| ||
| AC Output to Critical Load - Full Load | Amps* | 97 |
AC | Current 3 phase, 1 neutral, 1 ground |
|
|
OUTPUT |
|
|
|
Minimum conductor size | AWG or kcmil (ea) | 1/0 | |
D |
|
|
|
| * Full load, nominal | voltage |
|
Note: Refer to Figure A – 3 on system one line diagram for the bold letter callout locations.
Read and understand the following notes while planning your installation:
1.Refer to national and local electrical codes for acceptable external wiring practices.
2.Material and labor for external wiring requirements are to be provided by designated personnel.
3.For external wiring, use 90oC copper wire. See the appropriate column in Tables A and B. When wiring to an external battery cabinet, either 75 oC or 90 oC wiring may be used.
4.Wire ampacities are chosen from Table
5.A neutral feeder is required for both the main and bypass inputs to this system.
6.Refer to section 1 of this manual for installation instructions.
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation | |
| 164201396 REV A 07/11/2003 |