13.3 UPS System Output

DC Ripple

less than 1% voltage ripple

UPS Output Capacity

100% rated current at 0.8 power factor

Output Voltage

±1.5% (10100% load)

Regulation

 

Output Voltage

Less than 1%

Harmonic Content

 

Output Voltage Balance

Each phase may be loaded to 100% independently with

 

voltage regulation within stated tolerance.

Output Voltage Phase

120 degrees between phases ±0.01 degree

Displacement

 

Output Transients

< ±4% for 0 to 100% or 100% to 0% load change

Frequency Regulation

±0.1% free running

Synchronous to Bypass

No-break transfer

Frequency Slew Rate

1 Hz per second maximum

Overload Capacity

101% to 125% for 10 minutes (25C)

 

126% to 150% for 30 seconds

Maximum Output

200% RMS for 10 cycles without bypass

Capability

 

13.4 Environmental Specifications

Dimensions (W x H x D) mm (in.)

700 (27.6) x 1800 (70.9) x 750 (29.6)

Weight Kg (lb.) 80 kVA Model

333 (733)

Weight Kg (lb.) 120 kVA Model

340 (748)

Operating temperature

0 to 40˚C (32 to 104˚F)

Operating Altitude

1500 meters (5000 feet) with no derating

Storage Temperature

0 to 50˚C (32 to 122˚F)

Relative Humidity

Maximum 95%, non-condensing

Audible Noise with 100%/75% Load

65/63 dBA (80 kVA) 70/65 dBA (120 kVA)

EMI Suppression

IEC 62040-3 & FCC A

Electrostatic Discharge (ESD)

IEC 801-2

Immunity

 

Applicable Standards

UL 1778 (Computer Room Suitable)

13-2

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

 

164201396 REV A 071103