Table H. Definition of pin connections on JD2 (25 pin DB-25P/F)

Pin

Contact

Signal

 

Function

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Mains failure

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

ALARM

MNS

Mains present

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

Load on inverter

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

Message

LD-INV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

Battery low

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

Alarm

BATT_LOW

Battery OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

Load on Mains (BYPASS mode)

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

Message

LD_MNS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

Common Alarm

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

Alarm

COMMON_ALARM

No Alarm Condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

NC

 

Not Connected

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

For future use

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

For future use

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

PS_12

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

23

 

 

 

 

 

 

 

 

PS_12

 

+ 12V (Imax = 100 mA)

 

 

 

 

 

 

 

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

 

Not Connected

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

Not Connected

 

 

 

 

 

 

 

 

 

 

 

 

Contacts are rated at 60 volts maximum DC or 30 volts RMS AC, and 500 mA.

maximum current and should be supplied by a LVLE source in compliance with UL 1778

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

A-7

164201396 REV A 07/11/2003

 