Table J. Equipment Weight
Powerware Model |
| Weight | Kg (lbs.) |
| |
Shipping | Installed |
| Point Loading | ||
|
| ||||
9335 – 80 kVA | 360 (792) | 333 | (733) |
| 4 at 83 (183) |
9335 – 120 kVA | 367 (807) | 340 | (748) |
| 4 at 85 (187) |
5. The clearances required around the UPS system are shown in Table K.
Table K. System Clearances
From Front of Cabinet | 36 inches working space |
From Back of Cabinet | 30 inches working space |
From Right or Left side of Cabinet | ~0 inches clearance |
6. The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: | 0 – 40˚C. (32 – 104˚F.) |
Recommended Operating Range: | 20 – 25˚C. (68 – 77˚F.) |
Maximum Relative Humidity: | 95% |
The UPS ventilation requirements for heat removal are shown in Table L.
Table L. Air Conditioning or Ventilation Requirements
During Full Load Operation
Powerware 9335 80kVA and 120 kVA
Powerware Model | Input/Output Voltage | Heat Rejection | ||||
|
|
|
|
| BTU/hr x 1000/hr | |
|
|
|
|
|
|
|
9335 | – | 80 kVA | 480/480 | linear load pf = 0.8 | 14.0 | (3.5) |
9335 – 120 kVA | 480/480 | linear load pf = 0.8 | 20.8 | (5.2) | ||
9335 | – | 80 kVA | 480/480 | linear load pf = 1.0 | 16.4 | (4.2) |
9335 – 120 kVA | 480/480 | linear load pf = 1.0 | 24.6 | (3.1) | ||
9335 | – | 80 kVA | 480/480 100% | 17.7 | (4.4) | |
9335 – 120 kVA | 480/480 100% | 26.6 | (6.6) |
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation | |