Chapter 5: Management with the CLU
135
1. Highlight SMART and press the spacebar to toggle between Enable and
Disable.
2. Highlight SMART Poll Interval and press the backspace key to erase the
current value.
3. Type a new interval value in minutes.
1 to 1440 minutes (24 hours)
4. Press Ctrl-A to save your settings.
Enclosure Management
Enclosure Management includes information, status, settings and location. To
access Enclosure Management:
1. From the Main Menu, highlight Subsystem Management and press Enter.
2. Highlight Enclosure Management and press Enter.
To access FPU VPD information (vital product data on field replaceable units),
highlight FPU VPD Information and press Enter.
To access the current status of the power supplies, blowers, temperature or
voltage sensors, highlight the item you want and press Enter.
Enclosure Status

Enclosure Management

The current status of the power supplies, blowers, temperature or voltage
sensors:
1. From the Main Menu, highlight Subsystem Management and press Enter.
2. Highlight Enclosure Management and press Enter.
3. Highlight power supplies, blowers, temperat ure or voltage sensors and pres s
Enter.

Power Supply Units

This screen displays the operatio nal and fan status of VTrak’s two power
supplies.
PSU (power supply unit) status – Should show Power On and Functional
Fan Status – Should show Functional
Healthy Threshold – Minimum acce ptable fan speed
Current Fan Speed – Should be greater than the Healthy Threshold value
If any status differs from those listed above or the fan speed is below the Healthy
Threshold value, there is a fan/power supply malfunction. See “Chapter 6:
Maintenance” on page 167.